General signal elastic seat sealing gate valve

17 May, 2026

Product Overview
The general signal elastic seat sealing gate valve is applied to the automatic sprinkler fire pipeline system to monitor the water supply pipeline and can remotely indicate the valve opening.
General signal soft sealed gate valves and gate valves with opening indication are often used in fire water supply systems. If the installation position of the gate valve is high above the ground, a rising stem gate valve is generally selected, and the valve opening indication can be clearly seen. If the installation position is low, the valve opening indication can be clearly seen. Then it is necessary to choose a gate valve with an opening indicator.
Product Requirements
1. The signal valve should have an output "on" and "off" electrical signal device. During the process of the signal valve from fully open to closed, when the contact that outputs the "on" signal (valve open) is converted to the output "off" signal (valve closed), the flow rate at this conversion point should be greater than or equal to 80% of the fully open flow rate. After this point, the valve will continue to output the "off" signal (valve closed). The fully open flow rate is the flow value measured when the signal valve is fully opened at a constant population pressure.
2. The signal valve shall undergo overload capacity test according to standard regulations, and its electrical components shall not overheat or burn out
Phenomena such as destruction, pitting, and contact adhesion.
3. The signal valve shall undergo voltage endurance testing according to standard regulations. Under the specified test voltage, its
The voltage between moving parts and stationary parts (including the casing) should withstand for 60 seconds ± 5 seconds without breakdown.
4. The signal valve shall undergo insulation resistance testing according to standard regulations, and the insulation resistance between the following components shall be measured
It should be greater than 2M0.
(1) When the electric shock is disconnected, between the same level incoming and outgoing lines;
(2) Between each live component and the metal bracket (including the casing).
(3) The signal valve shall undergo contact resistance testing according to standard regulations, and the contact resistance between each pair of closed contacts of the switch shall be less than 0.01.